ZPB30A1 60W programmable load instructions

Reviewed in "Silicon Chip" March 2023 page 62
and "Practical Electronics" December 2024 page 62

This device (the module) tests power sources, which may be mains or battery
powered, with maximum 30V output.
A constant current load is drawn up to 9.99A (60W limit) and the output
voltage monitored.
If the output voltage drops below the preset threshold, the alarm condition
is triggered.

A separate stabilised 12VDC supply, capable of 500mA, is required for the
module's own internal operation.
It is connected by a 2.1mm coaxial barrel plug, centre positive.


Functions

The module has two functions (Fun), indicated as Fun1 and Fun2 on the 7-segment displays.

Fun1 draws the preselected current indefinitely.
Current draw can be varied during the test, but threshold voltage cannot.
If the voltage from the source under test drops below threshold, the alarm condition is entered but current continues to be drawn.
During the alarm condition, the current draw can be reduced but not increased.
Increasing the voltage from the source under test cancels the alarm.
If the voltage is already below threshold when the test starts, the alarm sounds immediately.
This function is suitable for soak-testing mains power supplies.

Fun2 draws the preselected current until the low-voltage alarm condition occurs, when the test stops.
Current draw can be varied during the test, but threshold voltage cannot.
Next, the accumulated charge/energy, drawn from the source under test, is displayed as amp-hours (Ah) and watt-hours (Wh).
This function is suitable for estimating the storage capacity of a battery.
The module is unable to display elapsed time, alternative provision must be made if this is required.
While the test is running, the source's output voltage is displayed. This would need to be recorded manually if preparing a discharge-over-time graph.

The source under test is connected to the two-way screw terminal, polarity as shown by the P+ and P- labels.
During high current draw, voltage measurement can be underestimated because of voltage-drop in the connecting leads.
Provision is made for a 4-wire (Kelvin) test lead where thin sense wires can be connected at the two-way V+ V- terminal (polarity as marked).
The other ends of the wires go directly to the output terminals of the source under test.
Because the sense wires carry such a tiny current, voltage-drop is no longer important.
If a sense voltage is detected, the L-4 LED lights.
Connection to the sense terminal is optional, if not required then the terminal is left open-circuit.

Controls and alarm

The tactile (red) ON OFF button starts and stops tests, silences the alarm in Fun2 and can put the module into configuration mode (see below).
The rotary knob selects the preset low voltage alarm threshold and adjusts current draw. It also selects parameters in configuration mode and cycles through battery capacity measurements (all described below). It can be clicked down (like a button).

The under-voltage alarm is indicated by the red LED flashing and, if enabled, repeated bleeping.

Configuration

Hold down the ON OFF button, then provide 12V operational power through the concentric barrel connector.
If the power is of too low a voltage, error code Po-L appears (dimly!) on the top display.
Otherwise, all 7-segment displays briefly illuminate, then the top display shows the presently selected function as Fun* where * is either 1 or 2 (remembered from the last time this was set).
Now release the ON OFF button.
The lower 7-segment display shows three dashes.
To change function, turn then click down the knob.
To retain function, just click down the knob.

The top display changes to either bEoF if the bleeper is turned off,
or bEon if it is on.
To change this, turn then click the knob.
To retain the setting, just click.

The top display changes to adjust the brightness of all the LEDs, showing tt-* where * is either 1 (dimmest), 2 or 3 (brightest).
To change this, turn then click the knob. The LEDs are seen to change in sympathy with the displayed setting.
To retain the setting, just click.

The module enters the selected function mode.

Function 1: indefinite length soak-test

Current draw and threshold voltage are set as follows.
Each click of the knob cycles through each of four digits on the 7-segment displays.
The active digit flashes, along with either the A LED (current in amps, lower display) or the V LED (voltage threshold, top display, ends in u since V is unavailable in 7-segment).
Between the displays lie two unmarked LEDs. The one adjacent to the active digit illuminates.
The active digit is changed by turning the knob. Access to the leftmost digit is by adjusting the digit to its immediate right, increasing past 9 or reducing below 0.
Once the required parameters have been set, wait briefly for the display to stop flashing.

Connect the source under test. The top display now shows the source's voltage.
Click ON OFF. The test now starts, with measured voltage continuing to be shown on the top display.
To stop the test, click ON OFF. To continue the test, click ON OFF again.
Refer to Functions (above) for current adjustment and alarm condition during tests.

Function 2: battery capacity

Set the current draw and voltage threshold as described above in Function 1.
Connect the source under test. The top display now shows the source's voltage.
Click ON OFF to attempt to start the test. If the source voltage is already below the alarm threshold, the top display shows Err2 but the test will not start (no current drawn). Click ON OFF to cancel the error message.

While the test is in progress, the top display cycles through Volts, Ah and Wh, each accompanied by illumination of the corresponding green LED.
The test can be paused by clicking ON OFF, resumed without loss of accumulated Ah and Wh by a further click.

To silence the alarm at the end of the test (when voltage drops below threshold, current draw ceases) click ON OFF.
Now turn the knob to cycle the top display through V (will be zero), total Ah and total Wh (designated by green LEDs, as above).

To zero the Ah and Wh accumulators, click ON OFF.
A further click of ON OFF starts a new test.

Error codes

The manufacturer's documentation describes further error codes, not already encountered above:
otP Excess temperature (of heat sink)
oPP Transient power supply voltage spike
Err3 Reverse polarity
Err6 Abnormal supply voltage
None of these were actually observed during the compilation of this document.


This page can be downloaded by web browsers.
Choose "Save page as" (usually in the File, Tools or Page menu).
The document consists of a single, simple HTML (.htm) file.

These instructions were compiled by actual observation of a Zhiyu ZPB30A1P V3.3 module.
November 2024.